Rheem Furnace: LP gas at high altitude: select orifice from drill size table

Updated · by Aurora Star Tech Inc.

LP gas at high altitude: select orifice from drill size table on a Rheem furnace: Propane has a consistent heating value, so picking an orifice at altitude is more of a table lookup than a calculation. The catch, which people trip on, is that this furnace uses 10 in W.C. at the orifice, not the 11 in W.C. used in the NFGC LP chart. So do not use the NFGC LP orifice sizes. You reduce sea level input by 4 percent per 1,000 ft, then pick the orifice from the LP drill size table. The table applies to 90 Plus models only.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 90 Plus LP gas models at altitude

Common causes of lp gas at high altitude: select orifice from drill size table

  • LP furnace going in at high elevation
  • Orifice table confusion between the NFGC chart and the furnace's own table
  • Ordering orifices for a conversion kit
  • After a move or a change in installation altitude

How to fix lp gas at high altitude: select orifice from drill size table: step by step

  1. Find the altitude band for the installation
  2. Read the reduced input per burner for that band from the LP orifice drill size table
  3. Select the drill size listed for that band
  4. Order the orifice using the part number format 62-22175-(drill size). Example: #60 drill is 62-22175-60; 1.10 mm is 62-22175-90
  5. Drill sizes available are 39 through 64, plus metric 1.10 mm (-90)
  6. Do not use the NFGC LP orifice sizes, they assume 11 in W.C.
  7. After fitting, verify manifold pressure and flame
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

96MDV

96MDV06096MDV07096MDV08596MDV100

Source: Rheem 96V series installation instructions, p. 82. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977