Rheem Furnace: Horizontal installation: external condensate trap and clamps
Horizontal installation: external condensate trap and clamps on a Rheem furnace: Horizontal installations require the condensate trap mounted externally below the unit. Mount the trap after the unit is at its installation point to avoid damage in transport. Hand-tighten screws when mounting the trap or drain coupling to protect the mounting flange. Allow at least 6 in. of clearance below the furnace. When horizontal, worm drive clamps on the flue transition or IDB couplings must sit above the level midline.
Applies to: Horizontal left and right conversions
How to fix horizontal installation: external condensate trap and clamps: step by step
- Mount the trap externally below the unit after the furnace is in place.
- Hand-tighten the trap and drain coupling screws.
- Keep at least 6 in. of clearance below the furnace.
- Position worm drive clamps on the flue transition and IDB couplings above the midline.
- Apply freeze protection if required.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V series installation instructions, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.