Rheem Furnace: General condensate and conversion rules
General condensate and conversion rules on a Rheem furnace: All conversions require condensate plumbing to slope in the direction of water flow. Hoses must be free of kinks. Plug or cap any unused hose taps when hose routing changes. The inducer coupling ships with a 10-20 degree tilt for upflow. When converted to downflow, rotate the inducer coupling as shown, at least 10 degrees from horizontal. The IDB coupling arrow must point in the exhaust flow direction when reinstalled.
Applies to: All field conversions
How to fix general condensate and conversion rules: step by step
- Slope all condensate plumbing in the direction of water flow.
- Remove kinks from all condensate hoses.
- Plug or cap unused hose taps.
- Rotate the inducer coupling for downflow, at least 10 degrees from horizontal.
- Reinstall the IDB coupling with the arrow pointing in the exhaust flow direction.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V series installation instructions, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.