Rheem Furnace: Field conversion: downflow zero-clearance
Field conversion: downflow zero-clearance on a Rheem furnace: Converts the furnace to downflow zero-clearance. Requires parts from the parts bag, conversion kit RXGY-CK and zero-clearance kit RXGY-ZK. Tools include an electric drill, 3/16" and 1/8" bits, pliers, flat-head screwdriver, 1/4" and 5/16" hex drivers, tubing cutter, PVC glue and primer and a hammer. Steps 1 to 4 are shown with the furnace in the as-shipped condition. Source page text is partly jumbled.
Applies to: 96V and 96MDV downflow zero-clearance conversion
How to fix field conversion: downflow zero-clearance: step by step
- Remove the elbow, both couplings and the flue transition. Retain the elbow and couplings for later use. Remove the coupling on the inducer with the elbow for easier removal.
- Remove the trap and hoses. Remove the two screws and pull the trap straight out. Retain hose D.
- Install the 2-5/8" flush mount plug.
- Remove the left 2-3/8" flush plug in the blower shelf and discard it.
- Move the right 2-3/8" flush mount plug from the blower shelf to the top plate.
- Move the .403" drain plug in the collector box.
- Follow the remaining zero-clearance steps for pipe assembly and collar gasket installation as shown in the kit drawings, using the parts listed for RXGY-ZK.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: Rheem 96V installation manual, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.