Rheem Furnace: Example: checking orifice size at high altitude (natural gas)
Example: checking orifice size at high altitude (natural gas) on a Rheem furnace: Worked example of orifice sizing for natural gas at altitude, using a 900 BTU/ft3 regional gas. These numbers are for the example only. Do not reuse them on another site, use the local heating value and the manual tables.
Applies to: Natural gas orifice sizing above 2,000 ft
Common causes of example: checking orifice size at high altitude (natural gas)
- Not a fault call. Reference example showing how altitude derating changes the orifice.
How to fix example: checking orifice size at high altitude (natural gas): step by step
- Calculate Q = I / H: 14000 / 900 = 15.56 ft3 per hour (I = sea level input per burner, H = heating value).
- Find the sea level orifice for 3.5 in. w.c. in NFGC Table E.1.1(a): #49.
- Find the orifice at 5000 ft using NFGC Table E.1.1(d) with 4% derate per thousand ft: #51.
- Find the orifice at 8000 ft using the same method: #52.
- On a real job, get the heating value from the gas utility, not from this example.
- Orifice changes and gas input adjustment are for a licensed gas technician.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V series installation instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.