Rheem Furnace: ECM blower will not run – power and communication checks (code 68)

Updated · by Aurora Star Tech Inc.

ECM blower will not run - power and communication checks (code 68) on a Rheem furnace: The communicating blower motor does not start on a heat, cool or fan call and the control shows 68.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces

Common causes of ecm blower will not run - power and communication checks (code 68)

  • No 115-120 VAC at the motor line connector
  • Pins not seated in the 5-pin or control connector
  • Control cable between P5 and the motor damaged
  • Failed motor module

How to fix ecm blower will not run - power and communication checks (code 68): step by step

  1. Unplug the 5-pin line voltage connector at the motor. With the door switch closed, check for 115-120 VAC between pins 4 and 5; line voltage should be there whenever the furnace is powered. No voltage: fix the wiring. Make sure every pin is fully seated, then plug it back in.
  2. Unplug the motor control connector from P5 on the control and put 24 VAC on pins 3 and 4 of the motor side. With the door switch closed the motor should run at about 75%.
  3. Motor runs in that test: the problem is the control or the control cable, not the motor.
  4. Motor does not run: check the control cable end to end and pin seating; if the wiring is good, replace the motor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96MDV040B30A96MDV060B30A96MDV070B30A96MDV085C50A96MDV100C50A96MDV115D50AR96VA0401317MSAR96VA0601317MSAR96VA0701317MSAR96VA0851521MSAR96VA1001521MSAR96VA1151524MSA

Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Diagnosing blower motor issues p.122, Fig. 62. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977