Rheem Furnace: ECM blower does not start on high heat after burners light

Updated · by Aurora Star Tech Inc.

ECM blower does not start on high heat after burners light on a Rheem furnace: Use this check when the burners light but the ECM blower does not start roughly 15 to 20 seconds later on high heat. Turn the power off before touching connectors or harnesses, and confirm 115 VAC and 24 VAC readings carefully with a meter, since both are present on the board. Do not assume the motor is bad. In many cases it is a connector, a dip switch setting or low voltage to the motor. Work in order and write down each reading.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 96V and 96MDV series furnaces with ECM blower

Common causes of ecm blower does not start on high heat after burners light

  • Loose or bad connections between control and ECM motor
  • Missing 24 VAC to the ECM control
  • Dip switch setting wrong
  • PFC choke wiring or failure
  • Low line voltage to motor

How to fix ecm blower does not start on high heat after burners light: step by step

  1. Check all connections between the control and the ECM motor with power off
  2. Check 24 VAC to the ECM control (4-pin connector, pins 1 and 4)
  3. Check dip switch settings against the instructions
  4. Check the PFC choke and its wiring, if present
  5. Check fault codes shown on the display
  6. Check line voltage to the motor (115 VAC)
  7. Make sure test mode dip switches are set correctly before continuing
  8. Return to normal dip switch settings when finished
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

Source: 96V series installation instructions, p. 121-122. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.