Rheem Furnace: Direct vent: two-pipe layout and intake separation
Direct vent: two-pipe layout and intake separation on a Rheem furnace: Direct vent. Two pipes. One brings combustion air in, one sends flue gas out. Exhaust has to sit at least 12 in above the intake on vertical runs, or flue gas gets pulled right back in. Keep the combustion air inlet at least 3 ft from any other gas or fuel-burning vent or clothes dryer vent, except for multiventing. Both pipes must end in the same atmospheric pressure zone. Mix those up and you get nuisance pressure switch trips and bad combustion.
Applies to: Direct vent installations (2-pipe)
Common causes of direct vent: two-pipe layout and intake separation
- Intake too close to the exhaust, so flue gas recirculates
- Intake near a dryer vent or another appliance vent
- Intake and exhaust terminated in different pressure zones
- Pressure switch trips and poor combustion traced back to the termination
How to fix direct vent: two-pipe layout and intake separation: step by step
- Make sure the exhaust outlet is at least 12 in above the intake on vertical runs
- Keep the combustion air inlet at least 3 ft from any other fuel-burning vent or dryer vent, unless multiventing
- Terminate intake and exhaust in the same pressure zone
- Check both terminals are clear of snow, leaves and screens
- Inspect for leaks at joints and support the pipes per the instructions
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: Rheem 96V installation instructions, p. 58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.