Rheem Furnace: Clearing lockouts
Clearing lockouts on a Rheem furnace: Soft lockouts (five-minute pressure switch, one-hour ignition/flame) and hard lockouts clear differently.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
How to fix clearing lockouts: step by step
- Any lockout clears when the cause is fixed and power is cycled off and on.
- Soft lockout only: remove the heat call for more than 2 but less than 20 seconds.
- Hard lockout from a dead blower (61 four times in one call) clears if you cycle the heat call; a 93 hard lockout does not.
- During lockout, cooling and continuous fan still run but the display shows the lockout code instead of C or F.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
More reset & cancel tips for furnace
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Lockout and replacing the furnace control p.121. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.