Rheem Furnace: Clear fault history with the pushbutton
Clear fault history with the pushbutton on a Rheem furnace: The fault buffer can be cleared from the furnace control pushbutton while the Fault History Display menu is active.
Applies to: 96V and 96MDV communicating furnaces
How to fix clear fault history with the pushbutton: step by step
- Open the Fault History Display (FL) menu.
- Hold the pushbutton for 5 seconds or more.
- Watch for segments A and D on the right-most displays to flash on and off for one second each, three times, which confirms the buffer is clear.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
More reset & cancel tips for furnace
Source: 96V installation instructions, p. 96. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.