Rheem Furnace: Alternate horizontal termination
Alternate horizontal termination on a Rheem furnace: The vent terminal sits 8 to 12 in from the wall. The vent tip portion must remain vertical. The vent may be rotated up to 45° left or right from vertical as long as the tip stays vertical. Maximum length shown is 60 in.
Applies to: Alternate horizontal non-direct vent termination
How to fix alternate horizontal termination: step by step
- Set the terminal 8 to 12 in from the wall.
- Keep the tip portion vertical.
- Rotate the vent no more than 45° left or right if needed.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V Series installation instructions, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.