Navien Combi Boiler: Run test mode (fan, pumps, valves, venturi)
Run test mode (fan, pumps, valves, venturi) on a Navien combi boiler: Test mode switches individual outputs so you can check them one at a time.
Applies to: NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H
How to fix run test mode (fan, pumps, valves, venturi): step by step
- Hold Back and Menu together for 3 seconds and choose 6. Test Mode.
- Fan Motor ramps the fan up to top speed and back down.
- 2-5. Boiler / Zone 1-3 pumps toggle on/off (zone pumps only in pump system).
- 6-8. Zone 1-3 valve output toggles (zone valve system only).
- 3 Way Valve Output toggles the 3-way valve.
- Flow Control Valve / 11. Mixing Valve drive open-closed-back and show FEEDBACK.
- Dual Venturi / 13. Recirc. Pump toggle on/off.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
NCB-190/060HNCB-190/080HNCB-240/110HNCB-240/130HNCB-250/150H
Source: Navien NCB-H Installation & Operation Manual, 11.6.6-11.6.8, p.125-128. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.