Navien Boiler: Wiring zone valves with 24 VAC powered thermostats
Wiring zone valves with 24 VAC powered thermostats on a Navien boiler: Same zone valve layout, with thermostats powered by 24 VAC. The boiler's internal 24 V transformer (75 VA) powers the zone valves, LWCO switches and thermostat terminals.
Applies to: NCB700 boilers with zone valves
How to fix wiring zone valves with 24 vac powered thermostats: step by step
- Connect zone valves 1 to 3 with NO/NC/COM as in the zone valve layout.
- Connect each thermostat to its 24 VAC line and neutral terminals.
- Check the total zone valve load does not exceed 72 VA; otherwise add an external zone valve controller.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 214. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.