Navien Boiler: Wiring zone valves (no 24 VAC supplied to valves)
Wiring zone valves (no 24 VAC supplied to valves) on a Navien boiler: A 3-zone valve system uses zone valves instead of zone pumps. Zone pump 3 terminal is used for the system pump. Each zone valve has a normally open (NO) and normally closed (NC) contact, with COM as the common.
Applies to: NCB700 boilers with zone valves
Common causes of wiring zone valves (no 24 vac supplied to valves)
- Total zone valve draw over 72 VA needs an external zone valve controller.
How to fix wiring zone valves (no 24 vac supplied to valves): step by step
- Connect zone valves 1 to 3 to their terminals (max 1 A each).
- Connect the system pump to the zone pump 3 terminal (max 2.5 A).
- Wire the recirculation pump (max 2.5 A) and boiler internal pump as shown.
- Set the valve contacts: NO means power is supplied when the valve is open; NC means power is supplied when the valve is closed.
- Do not use COM as a 24 VAC supply in this layout (it is not used).
- If the three zone valves draw more than 72 VA total, install an external zone valve controller.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 213. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.