Navien Boiler: Wiring zone pumps and dry-contact thermostats (no 24 VAC supplied)

Updated · by Aurora Star Tech Inc.

Wiring zone pumps and dry-contact thermostats (no 24 VAC supplied) on a Navien boiler: The NCB700 supports up to 3 heating zones. The zone pump and boiler pump connectors are dry contacts; the thermostats are wired without 24 VAC supplied by the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NCB700 boilers with 3 zone pumps

How to fix wiring zone pumps and dry-contact thermostats (no 24 vac supplied): step by step

  1. Connect zone pumps 1 to 3 to their dedicated pump terminals, and the boiler external pump to its terminal (each max 2.5 A).
  2. Connect line and neutral to each pump as shown in the diagram.
  3. Connect the boiler internal pump to its terminal (max 2.5 A).
  4. For a 24 V thermostat, connect it to terminals R and C on the boiler PCB.
  5. Use the C connection for an optional 24 V thermostat that has a common wire.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien NCB700 installation and operation manual, p. 209. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.