Navien Boiler: Venting requirements (Category IV, positive pressure)
Venting requirements (Category IV, positive pressure) on a Navien boiler: The boiler is a Category IV appliance and needs a special vent system. The vent operates under positive pressure. Improper venting can cause high carbon monoxide levels and serious injury or death. Vent systems must be installed only by licensed professionals.
Applies to: NCB700 venting
How to fix venting requirements (category iv, positive pressure): step by step
- Vent the exhaust gases directly outdoors using the approved vent materials and follow the venting instructions.
- Do not connect vents from naturally drafted gas appliances to any part of a mechanical positive-pressure vent system.
- Install the vent per the National Fuel Gas Code (ANSI Z223.1/NFPA 54) or CAN/CGA B149.1, and all local codes.
- Keep the vent system as short and straight as possible.
- Install the boiler as close as possible to the vent termination.
- Do not connect the boiler vent to the vent of another gas appliance or to a chimney.
- Slope horizontal vent runs upward toward the termination at 1/4 in per ft (2% slope).
- Seal every joint in the intake and exhaust vent, from the boiler connection to the termination, so it is gas-tight.
- Do not insulate non-metallic vent materials.
- Keep the intake and exhaust vent terminations clear of snow, ice and other obstructions. The building owner is responsible for this and for periodic maintenance.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation & operation manual, pp. 231-232. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.