Navien Boiler: Vent run slope and support
Vent run slope and support on a Navien boiler: Horizontal vent runs must rise toward the termination and be supported at set intervals.
Applies to: NCB700 series
How to fix vent run slope and support: step by step
- Slope horizontal runs up toward the termination at 1/4 in per foot (2% slope).
- Support exhaust and intake pipes at least every 4 ft (1.2 m), or closer if local code requires.
- Keep the vent run as short and straight as possible and place the boiler close to the termination.
If the unit shows an error code, look it up: Navien Boiler codes
More commissioning tips for boiler
Source: Navien NCB700 installation and operation manual, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.