Navien Boiler: Vent pipe insertion and connection
Vent pipe insertion and connection on a Navien boiler: Cut and deburr the vent pipe square before fitting. Lubricate the pipe end with water only, never grease. Do not use primer or adhesive on the boiler connection. Never put an elbow directly on the exhaust collar; start the vent run with a straight pipe length.
Applies to: NCB700 vent connection
How to fix vent pipe insertion and connection: step by step
- Mark the pipe 70 mm (2-3/4 in) from the end.
- Cut the pipe square at 90 degrees and deburr it.
- Lubricate the pipe end with water.
- Push the pipe into the collar with a twisting motion until it bottoms out, and the mark is no longer visible.
- Tighten the clamp with an 8 mm socket.
If the unit shows an error code, look it up: Navien Boiler codes
More commissioning tips for boiler
Source: Navien NCB700 installation and operation manual, p. 232-233. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.