Navien Boiler: Setting up cascade communication
Setting up cascade communication on a Navien boiler: Assign the NCB700 as main unit and allocate each NPE water heater as a sub unit.
Applies to: NCB700 main unit with NPE-A2 sub units
How to fix setting up cascade communication: step by step
- On the main NCB700 panel, press Back and Menu together for 3 seconds, then select 4. Cascade Status and Set.
- Turn the Command dial to move between parameters, or to change a value.
- Press the Command dial to select 1. Cascade System Setting, then select START.
- On the sub NPE-A2 panel, press and hold the OK button for 3 seconds. The display shows ID 1. Allocated! and a sub unit icon.
- Repeat for each remaining sub water heater. To add a sub unit later, repeat this step.
- On the main NCB700 panel, press the Command dial when the prompt appears. Configured heater displays return to temperature display.
- To reassign the main unit, repeat the whole procedure.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 87-88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.