Navien Boiler: RS-485 cable length and cable type
RS-485 cable length and cable type on a Navien boiler: Maximum RS-485 distance is about 3,000 ft at 57600 baud. Higher baud rates reduce the usable distance. Use twisted pair cable such as UTP or CAT5 for signal quality.
Applies to: Modbus RTU RS-485 network
How to fix rs-485 cable length and cable type: step by step
- Keep the run within the distance for the chosen baud rate.
- Use twisted pair cable (UTP or CAT5).
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien Modbus RTU installation & operation manual, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.