Navien Boiler: NaviClean magnetic filter: annual service
NaviClean magnetic filter: annual service on a Navien boiler: NaviClean is an in-line magnetic/dirt filter (made by ADEY) for hydronic systems. Best spot is after the last zone and before the boiler. It needs a yearly clean.
Applies to: Navien NaviClean hydronic filter
Common causes of naviclean magnetic filter: annual service
- Magnetite and debris build-up in the filter
How to fix naviclean magnetic filter: annual service: step by step
- It holds pressure and can be hot. Let it cool and release pressure before opening.
- Strong magnet: keep it away from phones and cards. Careful if you have a pacemaker.
- Turn both valves off.
- Open the vent to release pressure.
- Open the drain and let the debris out, then close it.
- Remove the cover and clean out the inside.
- Refit the cover. Do not overtighten.
- Turn the valves on, open the vent to bleed air, then close it.
- Optional: add ADEY MC1+ inhibitor through the filter.
- Limits: 87 psi max, 203°F max, up to 21 GPM. Connections 1 in. compression or 1-1/4 in. NPT adapters.
If the unit shows an error code, look it up: Navien Boiler codes
Source: NaviClean Installation and Service Manual 1807 (Navien / ADEY), p.1-2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.