Navien Boiler: Measuring and adjusting inlet gas pressure

Updated · by Aurora Star Tech Inc.

Measuring and adjusting inlet gas pressure on a Navien boiler: Check inlet gas pressure during the commissioning run and adjust the regulator if needed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NFB-301C/399C

How to fix measuring and adjusting inlet gas pressure: step by step

  1. Shut off the manual gas valve.
  2. Remove the front cover (4 latches).
  3. Loosen the test screw and connect a manometer to the pressure port. Zero the manometer first.
  4. Re-open the manual gas valve and check for leaks.
  5. Open multiple high-flow fixtures such as tub and shower faucets to bring the boiler to maximum firing.
  6. Read the inlet pressure and compare with NG 3.5 to 10.5 in WC or LP 8.0 to 13.0 in WC.
  7. If out of range, adjust the gas regulator on the gas supply.
  8. Reinstall the front cover when finished.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien NFB-C quick installation guide, p. 4. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.