Navien Boiler: LP gas conversion procedure (NCB-H)
LP gas conversion procedure (NCB-H) on a Navien boiler: Convert the boiler from natural gas to propane, then verify combustion.
Applies to: NCB-190/060H, NCB-190/080H, NCB-240/110H, NCB-240/130H, NCB-250/150H
How to fix lp gas conversion procedure (ncb-h): step by step
- Turn off gas and water supply to the boiler.
- Remove the front cover by releasing the four latches.
- Disconnect the gas inlet pipe from the gas valve at location A (two screws).
- Remove the four screws at location B and pull the gas valve off the fan assembly.
- Remove the two screws holding the gas orifice and swap in the LP orifice, making sure the packing is seated in the port.
- Refit the gas valve outlet adapter and all screws without overtightening.
- Inspect the gas valve O-ring and make sure it is in good condition and installed.
- Set DIP switch 2 #1 to ON for propane (or OFF for natural gas) and set switches 2 and 3 for altitude.
- Turn gas and water back on.
- Check CO2 at high fire and low fire, or check offset at low fire, and adjust only if out of range.
- Apply the conversion labels next to the rating plate after values are confirmed.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB-H LP gas and high altitude conversion guide, p. 1-2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.