Navien Boiler: Lost or incorrect gateway IP address
Lost or incorrect gateway IP address on a Navien boiler: Find the gateway on the network with the FieldServer Toolbox and correct its IP.
Applies to: Gateway Ethernet access
Common causes of lost or incorrect gateway ip address
- IP address unknown or changed
How to fix lost or incorrect gateway ip address: step by step
- Make sure FieldServer Toolbox is installed on the local PC; download it from the Sierra Monitor website if not.
- Connect a standard Cat-5 cable between the PC and the gateway Ethernet port.
- Open FS Toolbox Utility and click Discover Now.
- Note the gateway's IP address.
- To change it, click the settings icon on the gateway row, choose Network Settings, change the IP, and click Update IP Settings.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Modbus/BACnet Gateway Start-up Guide, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.