Navien Boiler: Leak testing the common vent
Leak testing the common vent on a Navien boiler: Test every joint on the common vent before the boiler is put into service.
Applies to: NCB700-190/060, NCB700-190/080, NCB700-240/110, NCB700-240/130, NCB700-250/150
How to fix leak testing the common vent: step by step
- Assemble the wye joint or wye assembly to the vent pipe with solvent cement on mating surfaces.
- Fill the system with water and turn the boiler on.
- Check every joint with a bubble test kit.
- If bubbles form, repair that section of pipe and bubble test it again.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 99. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.