Navien Boiler: Installing the pressure relief valve
Installing the pressure relief valve on a Navien boiler: The relief valve protects the heating circuit from overpressure and must be sized, placed and discharged correctly.
Applies to: NCB700 heating circuit relief valve
Common causes of installing the pressure relief valve
- Relief valve undersized for boiler input or system pressure rating
- Discharge pipe blocked or exposed to freezing
How to fix installing the pressure relief valve: step by step
- Only a licensed professional should install the relief valve.
- Mount the valve upright on the boiler, as close to the boiler as possible.
- Do not install any other valve between the relief valve and the boiler.
- Make sure the valve pressure capacity is at least the maximum heating system pressure rating.
- Make sure the valve BTU/H rating is at least the boiler maximum input.
- Route the discharge pipe so hot water cannot spray the operator or equipment, and end it 50 to 150 mm (2 to 6 in) above the floor or floor drain so discharge is visible.
- Do not connect the discharge pipe where it can freeze, and keep it clear of blockages.
- After filling and pressurizing, lift the lever to test the valve. Replace it right away if it does not work correctly.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation manual, p. 184. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.