Navien Boiler: Installing the Modbus RTU wiring

Updated · by Aurora Star Tech Inc.

Installing the Modbus RTU wiring on a Navien boiler: Field wiring of the Modbus RTU board to the building automation system (RS-485 network). Power off the boiler before opening it.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NFB700-500C/600C/800C/1000C

How to fix installing the modbus rtu wiring: step by step

  1. Turn off the power supply to the boiler.
  2. Release the 4 latches on the upper sides of the boiler and remove the upper-front cover.
  3. Connect the 3-pin terminal block on the right side of the front panel to the RS-485 device: A = RS-485 +, B = RS-485 -, G = RS-485 GND.
  4. If the RS-485 device needs power, wire it to the AC24VN and AC24VL ports of terminal block CNIN9 (the controller supplies 24VAC).
  5. For a BACnet or LonWorks gateway, follow the BACnet or LonWorks installation manual instead.
  6. In cascade systems, connect the RS-485 device to the front panel of the main unit.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien Modbus RTU installation & operation manual, p. 3. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.