Navien Boiler: Installing the DHW pressure relief valve

Updated · by Aurora Star Tech Inc.

Installing the DHW pressure relief valve on a Navien boiler: A DHW pressure relief valve must be fitted by a licensed professional. It is not supplied with the boiler and is required. Approved examples listed: Wilkins P-1000A (Zurn), Conbraco 17-402-04, Watts 3L (M7), Cash Acme FWL-2 3/4 in. Its discharge capacity must be at least the DHW system's maximum pressure rating, and its BTU/H rating must be at least the boiler's maximum input.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NCB700 DHW pressure relief valve

How to fix installing the dhw pressure relief valve: step by step

  1. Confirm the valve's discharge capacity meets or exceeds the DHW maximum pressure rating.
  2. Confirm the valve's BTU/H rating meets or exceeds the boiler's maximum input BTU/H.
  3. Install the valve as close to the boiler as possible. No other valve may sit between the relief valve and the boiler.
  4. Run the discharge line to within 2 to 6 in (50-150 mm) of the floor or a floor drain.
  5. Keep the discharge line free-draining with no reducing coupling or restriction.
  6. Route discharge so hot water cannot splash people or nearby equipment.
  7. Do not plug the valve. If it discharges periodically, check for thermal expansion in the closed supply and contact the water supplier or plumber.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien NCB700 installation and operation manual, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.