Navien Boiler: Ignition failure from flame rod or igniter buildup
Ignition failure from flame rod or igniter buildup on a Navien boiler: Ignition failures can happen when dirt or white powdery residue builds up on the flame rod. If ignition keeps failing, clean the flame rod. A new igniter gasket is required when the igniter is reinstalled, because a reused gasket can leak gas.
Applies to: NCB-H series
Common causes of ignition failure from flame rod or igniter buildup
- Buildup of dirt or white powdery residue on the flame rod (sensor)
How to fix ignition failure from flame rod or igniter buildup: step by step
- Turn off the power to the unit.
- Remove the igniter.
- Clean the flame rod with emery cloth and note the white powdery residue on the sensor.
- Reinstall the igniter with a new igniter gasket. Never reuse the old gasket.
- Turn the power back on and check ignition during operation.
- If ignition failure continues, contact Navien technical support.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB-H emergency kit quick guide, p. 1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.