Navien Boiler: High altitude derate and conversion
High altitude derate and conversion on a Navien boiler: Above 2,000 ft the boiler derates. Natural gas needs an orifice change above 5,400 ft. Propane needs the propane conversion kit at any elevation the unit is used at.
Applies to: Gas type and elevation changes
How to fix high altitude derate and conversion: step by step
- Set DIP SW 2 for the install elevation.
- Above 2,000 ft, expect a 3% derate per 1,000 ft on natural gas.
- Above 2,000 ft, expect a 4% or more derate per 1,000 ft on propane.
- For natural gas above 5,400 ft, change the gas orifice to the high altitude orifice. Do not confuse it with the LP orifice.
- For propane at any altitude up to 10,100 ft, use the Propane Gas and High Altitude Conversion Kit.
- The natural gas high altitude kit is inside the cabinet. Remove the front cover to reach it.
- Check the orifice against the Natural Gas High Altitude Conversion Guide and replace it if required.
- Common vent installs are only approved up to 4,500 ft.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 78-79. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.