Navien Boiler: Heating system piping, expansion tank and fill
Heating system piping, expansion tank and fill on a Navien boiler: Flush the whole system before connecting piping and keep debris out of the lines. Expansion tank and fill connection must be placed correctly.
Applies to: NCB700 space heating system
How to fix heating system piping, expansion tank and fill: step by step
- Flush the system to remove flux, solder, sediment and debris before connecting the boiler
- Clean the heating return strainer after the boiler is installed
- Size the expansion tank to the system water volume and fill pressure
- Connect the air separator to the expansion tank only if the separator is on the pump suction side
- Place the expansion tank and fill connection on the pump suction side
- Make sure the expansion tank cannot be isolated from the boiler while the system runs
- On diaphragm tanks, install an automatic air vent above the tank
- Repair leaks right away to avoid adding make-up water, which brings air and minerals into the system
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 184-187. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.