Navien Boiler: Hardwiring the boiler directly to the power supply (no plug)
Hardwiring the boiler directly to the power supply (no plug) on a Navien boiler: Used only where local code requires direct wiring. Remove the factory plug and splice the boiler leads to a field-supplied 110-120V supply.
Applies to: NCB700 boilers wired without the factory plug
How to fix hardwiring the boiler directly to the power supply (no plug): step by step
- Disconnect the power supply to the boiler.
- Cut the factory power cord about 2 in. below the bottom of the cabinet and discard the cord.
- Remove the 4 screws holding the front cover and open it.
- Locate the black (hot), white (neutral) and green (ground) wires connected to the cord. Cut them as close as possible to where the cord ends.
- Strip about 1/2 in. of sheathing from each wire.
- Connect the 110-120V AC supply conductors to the bare wires with field-supplied twist-on connectors or wire nuts.
- Make sure the boiler is grounded. Do not use gas or water pipes as the ground path.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.