Navien Boiler: Gas supply piping checks
Gas supply piping checks on a Navien boiler: Gas connection rules to follow before the boiler is started.
Applies to: NCB700 condensing combi-boiler
How to fix gas supply piping checks: step by step
- Measure the gas supply pressure at the main line and clear any debris from the gas line before connecting.
- Size the gas line and connection using the gas pipe sizing tables. Connections are 3/4 in. A 1/2 in rigid pipe is allowed only where local codes permit it.
- Do not use 1/2 in corrugated connectors or hoses, because they can cause noise. Keep flexible lines free of kinks.
- Use two wrenches on boiler gas fittings: one to hold the boiler connector and one to tighten the fitting.
- Support the gas piping separately. The boiler and its accessories must not carry the pipe weight.
- Install a manual gas shutoff valve between the supply line and the boiler.
- Where possible, connect the boiler as the first appliance downstream of the gas meter. The meter capacity must be at least the total connected appliance load.
- Leak test the boiler and gas connections with a bubble solution. Never use a flame to find leaks.
- If a leak is found, shut the boiler and gas off and repair it before restarting.
If the unit shows an error code, look it up: Navien Boiler codes
More commissioning tips for boiler
Source: Navien NCB700 installation and operation manual, p. 63-64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.