Navien Boiler: Gas supply connection and leak test
Gas supply connection and leak test on a Navien boiler: Gas supply must be connected by a licensed professional using the gas type and pressure on the rating plate. The boiler cannot be converted between natural gas and propane without a Navien gas conversion kit.
Applies to: NCB700 all models
How to fix gas supply connection and leak test: step by step
- Determine gas type and pressure from the rating plate.
- Perform a pressure test on the main gas supply line.
- Purge the gas line of debris.
- Size the gas line using the tables that follow.
- Install a certified full port valve on the gas supply line and on the boiler.
- Install a manual gas shut-off valve and a sediment trap close to the boiler gas connection.
- Connect the gas supply line; use two wrenches to avoid damaging the boiler connector.
- Leak test all connection points and the boiler using a bubble test, never a flame.
If the unit shows an error code, look it up: Navien Boiler codes
Source: NCB700 Installation & Operation Manual, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.