Navien Boiler: Connecting the vent pipe to the vent collar
Connecting the vent pipe to the vent collar on a Navien boiler: Correct insertion and clamping of the exhaust pipe onto the boiler collar.
Applies to: NCB700 series
How to fix connecting the vent pipe to the vent collar: step by step
- Cut the vent pipe square (90°) and deburr it.
- Lubricate the pipe end with water only. Do not use grease, primer or cement on the appliance connection.
- Mark the pipe 2-3/4 in (70 mm) from its end.
- Start the run with straight pipe. Do not use a street elbow at the collar.
- Push the pipe in with a twisting motion until it bottoms in the collar, leaving the mark hidden.
- Tighten the clamp with an 8 mm socket.
- Turn on the boiler and bubble-test all exhaust joints for gas leaks.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 61-62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.