Navien Boiler: Connecting the vent pipe to the common vent collar
Connecting the vent pipe to the common vent collar on a Navien boiler: Seat the vent pipe fully in the collar and secure it so the joint is gas-tight.
Applies to: NCB700-190/060, NCB700-190/080, NCB700-240/110, NCB700-240/130, NCB700-250/150
How to fix connecting the vent pipe to the common vent collar: step by step
- Cut the pipe square at 90 degrees and deburr it before fitting.
- Mark the pipe 1-1/2 in (38 mm) from its end.
- Lubricate the pipe end with water only. Do not use grease.
- Push the pipe into the collar with a twisting motion until it bottoms out. The mark should disappear.
- Tighten the four mounting screws supplied with the collar.
- Do not use primer or cement on the appliance connection.
- With the front cover removed, connect the supplied VID jumper wire to the wire labelled VID.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 97. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.