Updated · by Aurora Star Tech Inc.

Connect the NFB-301C/399C boiler to the gateway R1 port on a Navien boiler: The R1 port takes the boiler RS-485 link through a 3-pin Phoenix connector that plugs into the boiler terminal block on the right side of the front panel. Use standard RS-485 grounding.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NFB-301C and NFB-399C boilers connected to gateway R1

How to fix connect the nfb-301c/399c boiler to the gateway r1 port: step by step

  1. Make sure R1 DIP switch 4 is OFF.
  2. Connect the gateway R1 3-pin Phoenix connector to the 3-pin terminal block on the boiler front panel.
  3. Match the pins: gateway A (TX+) to boiler +, gateway B (RX-) to boiler -, gateway G (GND) to boiler GND.
  4. Use standard grounding practice for the RS-485 GND.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Modbus/BACnet Gateway Start-up Guide, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.