Navien Boiler: Connect the NFB-301C/399C boiler to the gateway R1 port
Connect the NFB-301C/399C boiler to the gateway R1 port on a Navien boiler: The R1 port takes the boiler RS-485 link through a 3-pin Phoenix connector that plugs into the boiler terminal block on the right side of the front panel. Use standard RS-485 grounding.
Applies to: NFB-301C and NFB-399C boilers connected to gateway R1
How to fix connect the nfb-301c/399c boiler to the gateway r1 port: step by step
- Make sure R1 DIP switch 4 is OFF.
- Connect the gateway R1 3-pin Phoenix connector to the 3-pin terminal block on the boiler front panel.
- Match the pins: gateway A (TX+) to boiler +, gateway B (RX-) to boiler -, gateway G (GND) to boiler GND.
- Use standard grounding practice for the RS-485 GND.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Modbus/BACnet Gateway Start-up Guide, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.