Navien Boiler: Connect NFB-301C/399C boiler to gateway R1 port
Connect NFB-301C/399C boiler to gateway R1 port on a Navien boiler: Wire the boiler's front-panel 3-pin terminal block to the gateway R1 Phoenix connector. Keep R1 Switch 4 OFF and bond RS-485 GND per standard practice.
Applies to: NFB-301C/399C boiler to gateway R1
How to fix connect nfb-301c/399c boiler to gateway r1 port: step by step
- Set R1 DIP Switch 4 to OFF.
- Connect the gateway R1 3-pin Phoenix connector to the boiler's 3-pin terminal block on the right side of the front panel.
- Wire A to TX+ / RS-485+, B to RX- / RS-485-, and G to RS-485 GND.
- Use standard grounding principles for the RS-485 GND connection.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien Modbus/BACnet gateway installation and operation manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.