Navien Boiler: Connect NFB-301C/399C boiler to gateway R1 port

Updated · by Aurora Star Tech Inc.

Connect NFB-301C/399C boiler to gateway R1 port on a Navien boiler: Wire the boiler's front-panel 3-pin terminal block to the gateway R1 Phoenix connector. Keep R1 Switch 4 OFF and bond RS-485 GND per standard practice.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NFB-301C/399C boiler to gateway R1

How to fix connect nfb-301c/399c boiler to gateway r1 port: step by step

  1. Set R1 DIP Switch 4 to OFF.
  2. Connect the gateway R1 3-pin Phoenix connector to the boiler's 3-pin terminal block on the right side of the front panel.
  3. Wire A to TX+ / RS-485+, B to RX- / RS-485-, and G to RS-485 GND.
  4. Use standard grounding principles for the RS-485 GND connection.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien Modbus/BACnet gateway installation and operation manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.