Navien Boiler: Condensate drain installation
Condensate drain installation on a Navien boiler: Condensate is acidic, with a pH of 3 to 5. Drain it to a laundry sink or through a neutralizer, or pump it if the drain is far or below the boiler outlet.
Applies to: NCB700 condensate drain
How to fix condensate drain installation: step by step
- Connect a corrosion-resistant drain line (PVC or CPVC) to the 1/2 in NPT fitting at the bottom of the boiler
- Do not reduce the fitting or drain line below 1/2 in
- Fill the condensate trap with water after installing the drain line
- Slope the drain line down at least 1/4 in per foot if no pump is used
- Use a condensate pump rated for at least 2 gallons per hour per boiler when a pump is used
- Make sure the drain is not blocked or restricted
- If a neutralizer is used, inspect it every few months during the first year and replace it as needed
- Never let people or animals drink the condensate
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 191-192. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.