Navien Boiler: Closed loop system requirements and air removal
Closed loop system requirements and air removal on a Navien boiler: The boiler is only for pressurized closed loop heating systems that are free of air and debris. Open systems are not approved.
Applies to: NCB700 space heating system
Common causes of closed loop system requirements and air removal
- Air trapped in the system
- Low water level or blocked air vent cap
- Leaks causing repeated makeup water
How to fix closed loop system requirements and air removal: step by step
- Do not use the boiler on open systems or for direct heating of potable water.
- Confirm the system is closed and pressurized, with water pressure of 12 to 30 psi at the boiler outlet.
- Install air bleed devices of the right size at strategic points across the heating system, as shown in the piping examples.
- Purge all air during commissioning.
- Check the water level is correct and the air vent cap is not blocked.
- Repair any leak immediately to avoid adding makeup water, since fresh water brings air and minerals that can fail the heat exchanger.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation manual, p. 183-184. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.