Navien Boiler: Cleaning the intake air filter
Cleaning the intake air filter on a Navien boiler: A dust- or pollen-blocked intake air filter stops the boiler and shows Error code 10. Clean it every 3 to 4 months.
Applies to: CH combination boiler
Common causes of cleaning the intake air filter
- Intake air filter blocked by dust or pollen
How to fix cleaning the intake air filter: step by step
- Locate the air filter above the fan, under the intake air duct in the top left corner of the boiler.
- Remove the single Philips screw securing the duct. Note which screw was removed.
- Pull the duct out toward the front.
- Remove the intake air filter from the bottom of the intake air duct.
- Separate the filter screen from the plastic assembly.
- Clean the filter and screen with a toothbrush and water.
- Refit the screen into the plastic assembly.
- Fit the filter and frame onto the bottom of the intake air duct.
- Reinstall the duct and screw.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien CH User's Operation Manual, p. 37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.