Navien Boiler: Check common vent collar damper through maintenance port
Check common vent collar damper through maintenance port on a Navien boiler: Periodic check of the damper plate inside the Navien common vent collar kit to confirm it opens and closes properly.
Applies to: NCB700 with Navien common vent collar kit (back-draft damper)
How to fix check common vent collar damper through maintenance port: step by step
- Remove the fix screw that holds the maintenance port cover to the common vent collar kit.
- Remove the gasket and the maintenance port cover.
- Look through the maintenance port at the damper plate. It should show OPEN when the boiler is firing and CLOSED when it is off.
- If the damper does not open or close properly, replace the common vent collar kit.
- If condensate comes out of the port, check drainage and look for blockage.
- Reinstall the gasket and the maintenance port cover, then secure with the set screw.
- Visually confirm the gasket sits correctly between the port and the cover.
- Warning: the gasket must be properly installed under the cover. Exhaust gas can leak if it is missing or seated wrong, causing carbon monoxide hazard.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 106. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.