Navien Boiler: Check CO2 at high fire and verify gas orifice
Check CO2 at high fire and verify gas orifice on a Navien boiler: Verify CO2 at high fire. If it does not match the table, do not change the gas valve. Check the gas orifice instead.
Applies to: NCB700 boilers during gas conversion or commissioning
Common causes of check co2 at high fire and verify gas orifice
- CO2 at high fire does not match Table 2
- Incorrect gas orifice installed
How to fix check co2 at high fire and verify gas orifice: step by step
- Open several DHW fixtures on full hot.
- Set the boiler to 2-stage D. MAX mode (see 12.6.7 Setting the Special Operation Modes).
- Measure CO2 at high fire.
- Compare the reading to Table 2.
- If CO2 does not match, do not adjust the gas valve. Check for the proper gas orifice.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 144. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.