Navien Boiler: Check and adjust gas/air ratio at low fire
Check and adjust gas/air ratio at low fire on a Navien boiler: Verify CO2 or offset at low fire and adjust the gas valve set screw if needed.
Applies to: NCB700 gas/air ratio
How to fix check and adjust gas/air ratio at low fire: step by step
- Open several DHW fixtures on full hot and set the boiler to 1-stage MIN mode.
- Remove the plate and gasket to reach the emissions port, then insert the combustion analyzer.
- Measure CO2 at low fire and compare it to Table 2.
- If CO2 is outside 0.5% of the table value, remove the screw-on cover over the set screw.
- Using a 5/32 in or 4 mm Allen wrench, turn the set screw no more than 1/4 turn clockwise to raise or counterclockwise to lower CO2.
- Turn on the gas and water supply, then leak test all gas connections before operation.
- If using a digital manometer, loosen the offset port screw two turns and connect the positive side to the offset pressure port.
- Compare the low fire offset with Table 3 and adjust the set screw the same way if it is out of range.
- Set 2-stage D. MAX and check CO2 at high fire. If it does not match Table 2, do not adjust the gas valve; check the gas orifice.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 143. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.