Navien Boiler: Bias resistor DIP switches on R1 and R2

Updated · by Aurora Star Tech Inc.

Bias resistor DIP switches on R1 and R2 on a Navien boiler: Bias resistors hold an idle RS-485 bus in a known state. They are 510 ohm and should be enabled at only one point on the bus. Power cycle the gateway after changing them.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: R1 and R2 ports

How to fix bias resistor dip switches on r1 and r2: step by step

  1. Move both the BIAS- and BIAS+ DIP switches to the right on the port being set (R1 or R2) to enable bias resistors.
  2. Enable bias on only one device on the bus, typically the field port end.
  3. Power cycle the gateway if it is already powered, because DIP changes do not take effect until then.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

More other tips for boiler

Source: Navien Modbus/BACnet gateway installation and operation manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.