Navien Boiler: Assembling the wye joint on the common vent
Assembling the wye joint on the common vent on a Navien boiler: Build the vent run from the collar using wye fittings. Tees can be used instead of wyes.
Applies to: NCB700-190/060, NCB700-190/080, NCB700-240/110, NCB700-240/130, NCB700-250/150
How to fix assembling the wye joint on the common vent: step by step
- Cement a hub wye, 2 in reducer and 90 degree elbow together, or use a hub reducing wye and 90 degree elbow.
- Slide the vent pipe fully into the collar until it contacts the bottom of the socket.
- Tighten the collar clamp with an 8 mm socket to seal the joint.
- Start the vent run with a length of straight pipe. Never start it with a street elbow at the collar.
- Keep the pipe from the unit to the main trunk within 16 ft equivalent length.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 98. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.