Applies to: Propane gas/air ratio check

How to fix adjust gas/air ratio with digital manometer: step by step

  1. Connect the digital pressure manometer to the port as shown in the manual (Figure 8). Use the positive side of a dual port manometer.
  2. Activate multiple zones and set the boiler to the required mode.
  3. Compare the reading with the value in the pressure table (-0.02 in ±0.01 in for propane).
  4. If the value is out of range, locate the set screw and turn it no more than 1/4 turn clockwise to adjust the gas valve.
  5. Use a 5/32 in or 4 mm Allen wrench. Remove the screw-on cap to reach the set screw.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien NFC-H propane and high altitude conversion guide, p. 2. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.