Navien Air Conditioner: PCB detects overcurrent
PCB detects overcurrent on a Navien air conditioner: The PCB detected compressor or system current above the protection threshold. No code number is printed for this fault on these pages.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
Common causes of pcb detects overcurrent
- Defective compressor or system
How to fix pcb detects overcurrent: step by step
- Use a clamp meter to measure the AC current to the compressor.
- Compare the reading with the check value for this model on item 20 of the PCB.
- If the difference between the clamp meter reading and the check value is more than ±10%, the compressor or system has a fault.
- If the difference is large, replace the PCB.
- Check that the motor and compressor wiring is tight.
- Check the system for restrictions and refrigerant charge.
If the unit shows an error code, look it up: Navien Air Conditioner codes
Source: Navien NAA air conditioner service manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.