Navien Air Conditioner: Check for air or nitrogen contamination in the system
Check for air or nitrogen contamination in the system on a Navien air conditioner: Method to tell whether non-condensable gas is in the refrigerant circuit.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
Common causes of check for air or nitrogen contamination in the system
- Air or nitrogen left in the system after service
- Non-condensable gas raising high-side pressure
How to fix check for air or nitrogen contamination in the system: step by step
- Run the system until stable, about 10 to 15 minutes.
- Measure the high-side pressure and the condensing temperature.
- Look up the condensing temperature on the refrigerant P-T chart to get the saturation pressure.
- Compare the measured pressure with the saturation pressure.
- If the measured pressure is much higher than saturation pressure, air or nitrogen is likely present. Evacuate, refill refrigerant and add refrigeration oil.
If the unit shows an error code, look it up: Navien Air Conditioner codes
Source: Navien NAA air conditioner service manual, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.