Lennox Air Conditioner: Simulate a refrigerant leak with the RDS Test button
Simulate a refrigerant leak with the RDS Test button on a Lennox air conditioner: After the 5-minute purge, pressing Test during a call makes the board act as if a leak was found, which checks wiring and response.
Applies to: Lennox EL16KC1 A/C with RDS blower control board 27A02 (R-454B)
How to fix simulate a refrigerant leak with the rds test button: step by step
- Restore power and wait for the 5-minute purge to finish.
- Cooling check: start a cooling call at the thermostat, press Test on the RDS board, and confirm the LED flashes blue, the blower runs and the outdoor compressor stops.
- Press Test again to end the simulated leak.
- Heating check (gas furnace): start a heat call, press Test, and confirm the blue flashing LED, blower on, burners off and compressor off. Press Test again to end it.
If the unit shows an error code, look it up: Lennox Air Conditioner codes
Models
EL16KC1-018-230AEL16KC1-024-230AEL16KC1-030-230AEL16KC1-036-230AEL16KC1-041-230AEL16KC1-042-230AEL16KC1-047-230AEL16KC1-048-230AEL16KC1-060-230A
Source: Lennox EL16KC1 (Elite A-C, R-454B) Installation Instructions 100121 (01-2025), Start-Up Test Procedure (RDS Blower Control Board), printed p.35-36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.